NOV-IE1500 PV Insulation & Earth Continuity Tester (1500 V)
1500 V insulation tester for PV systems. Measures positive and negative pole-to-earth insulation at the same time, locates ground faults inside a string, and checks protective-earth continuity at 200 mA, with no plant shutdown needed.
Insulation faults are among the most common causes of inverter trips and lost yield in PV plants. The NOV-IE1500 finds them fast. In DUAL mode it measures the insulation resistance of both poles to earth in a single test, with no external shorting switch. GFL mode then pinpoints the faulty module or connector inside the string. RPE mode checks protective-earth continuity at 200 mA, and PI / DAR indices show whether insulation is ageing. Clear OK / NO verdicts make results easy for any technician to interpret.
Key features
1 DUAL mode: positive and negative pole-to-earth insulation in one test
2 Ground-fault locator (GFL): pinpoints the faulty module, cable or junction box in a string
3 Up to 1500 V DC: test voltages of 250 / 500 / 1000 / 1500 V, plus timed testing
4 RPE continuity at 200 mA: with instant OK / NO verdict
5 PI and DAR indices: assess insulation ageing
6 No shutdown needed: tests live strings directly, with no external shorting switch
Specifications
| Function | Range | Resolution | Accuracy |
|---|---|---|---|
| DC voltage | 3 – 1500 V | 1 V | ±(1% rdg + 2 V) |
| AC voltage (TRMS) | 3 – 1000 V | 1 V | ±(1% rdg + 3 V) |
| Insulation, DUAL mode | 0.10 – 0.99 MΩ | 0.01 MΩ | ±(5% rdg + 5 dgt) |
| 1.0 – 19.9 MΩ | 0.1 MΩ | ±(5% rdg + 5 dgt) | |
| 20 – 100 MΩ | 1 MΩ | ±(5% rdg + 5 dgt) | |
| Insulation, TIMER mode | 0.10 – 9.99 MΩ | 0.01 MΩ | ±(5% rdg + 5 dgt) |
| 10.0 – 100 MΩ | 0.1 MΩ | ±(5% rdg + 5 dgt) | |
| Insulation test voltages | 250 / 500 / 1000 / 1500 V DC | ||
| Continuity (RPE) | 0.00 – 9.99 Ω | 0.01 Ω | ±(2% rdg + 2 dgt) |
| 10.0 – 100 Ω | 0.1 Ω | ±(2% rdg + 2 dgt) | |
| 100 – 1999 Ω | 1 Ω | ±(2% rdg + 2 dgt) | |
| RPE test current | 200 mA | ||
| Additional functions | GFL fault location, PI, DAR, OK / NO verdict | ||
| Certification | CE |
In the box
- NOV-IE1500 main unit
- 4 × colour-coded test leads with crocodile clips
- MC4 adapter connectors (red / black)
- PC software with USB cable
- Carry bag with shoulder strap
- External battery charger
- Hard carrying case
- 2 × 20 m extension leads with banana plugs
- Calibration certificate
- User manual
Applications
- IEC 62446-1 commissioning tests on PV strings, combiner boxes and inverters
- Tracing insulation faults behind inverter isolation alarms
- Detecting insulation degradation from moisture, dust and damaged cables
- Insulation testing of cables, transformers and switchgear
- EV battery packs and high-voltage DC bus monitoring